Performance analysis of a solar cooling plant based on a liquid desiccant evaporative cooler.

Author(s) : ARMANASCO F., COLOMBO L. P. M., LUCCHINI A., et al.

Type of article: Article, IJR article

Summary

Summer air conditioning represents a growing market in buildings worldwide, with a significant growth rate observed in European commercial and residential buildings. Available heat driven cooling technologies can be used in combination with solar thermal collectors to reduce the load caused by air conditioning on the electric utilities and to reduce the environmental impact. This work reports a performance analysis of an open cycle solar cooling plant. The plant, installed in Northern Italy, is based on a liquid desiccant evaporative cooler coupled with a solar field. Experimental tests run during summer show average primary energy ratio and primary energy saving index of about 1.6 and 30%, respectively. Though this performance is satisfactorily, the regeneration unit always operated near the lower bound of the nominal temperature range. Therefore, optimization of the solar system design could lead to higher performance

Available documents

Format PDF

Pages: 163-176

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance analysis of a solar cooling plant based on a liquid desiccant evaporative cooler.
  • Record ID : 30014277
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 53
  • Publication date: 2015/05