IIR document

Performance study of double corrugated cross-flow air-cooled plate heat exchangers.

Author(s) : KIM M., BAIK Y. J., KWON H. K., et al.

Summary

Experimental study on a cross-flow air-cooled plate heat exchanger (PHE) was performed. The two types of PHEs were manufactured with single-wave plates and double-wave plates in parallel. Cooling air flows through the PHEs in a crosswise direction against internal cooling water. The heat exchanger aims to substitute open-loop cooling towers with closed-loop water circulation, which guarantees cleanliness and compactness. In this study, prototype single-wave and double-wave PHEs were designed and tested in a laboratory scale experiments. From the tests, the double-wave PHE shows approximately 50% enhanced heat transfer performance compared to the single-wave PHE. However, the double-wave PHE costs 30% additional pressure drop. For the commercialization, a wide channel design for air flow would be essential for reliable performance.

Available documents

Format PDF

Pages: 2009-5

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance study of double corrugated cross-flow air-cooled plate heat exchangers.
  • Record ID : 2009-1983
  • Languages: English
  • Source: 3rd Conference on Thermophysical Properties and Transfer Processes of Refrigerants
  • Publication date: 2009/06/23

Links


See other articles from the proceedings (66)
See the conference proceedings