Sensitivity analysis of night cooling with natural ventilation.
Author(s) : PAASSEN A. H. C. van, GRÖNINGER B. P., REE H. van der
Summary
A dynamic simulation of the ventilation processes and the thermal behaviour of an office building is developed. This is used to investigate two aspects of night cooling with natural ventilation: the control strategies and the required ventilation opening area. The allowable internal heat gain for a high inertia is 27-33 W/m2. For a medium inertia building this is 22-26 W/m2. Night cooling with natural ventilation is not suitable for a light inertia building. Based on the outputs of large series of simulation runs, two user friendly design tools are developed: a graphical chart and a set of simplified equations.
Available documents
Format PDF
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Sensitivity analysis of night cooling with natural ventilation.
- Record ID : 2000-1521
- Languages: English
- Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Publication date: 1999/09/19
Links
See other articles from the proceedings (447)
See the conference proceedings
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Night; Building; Natural ventilation; Ventilation; Thermal inertia; Air conditioning
-
Evaluation of the energy conservation effect by...
- Author(s) : MISAKA I., HIGUCHI M., TAKAHASHI N., et al.
- Date : 2001/07
- Languages : Japanese
- Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 82
View record
-
Potencial de la ventilación natural nocturna: v...
- Author(s) : SÁNCHEZ DE LA FLOR F. J., ÁLVARES DOMÍNGUEZ S., SANZ FERNÁNDEZ J. A., et al.
- Date : 2006/11/20
- Languages : Spanish
View record
-
Kühlung von Gebäuden ohne Kältemaschine: Entwic...
- Author(s) : LÜDEMANN B., DETZER R., THIEL P., et al.
- Date : 2007/03
- Languages : German
- Source: Heiz. Lüft. Haustech. - vol. 58 - n. 3
View record
-
Thermal mass and night ventilation - utilising ...
- Author(s) : BARNARD N.
- Date : 2002/10
- Languages : English
- Source: Int. J. Vent. - vol. 1 - n. 2
View record
-
Stack ventilation and cooling for urban sites: ...
- Author(s) : GAGE S. A.
- Date : 1997/09/23
- Languages : English
- Source: Ventilation and cooling. Proceedings of the 18th AIVC Conference.
View record