IIR document

Study on heat transfer of finned tube heat exchanger for cryogenic liquid.

Author(s) : CHEN G., CHEN S., CHANG K., et al.

Summary

The heat transfer process of cryogenic liquid was studied. A group of variation curves of temperature vs. time were got through a gasification experiment of cryogenic liquid in a finned tube heat exchanger. A method of zoning calculation for gasification heat transfer process was proposed through analyzing the curves. Gasification process was divided into four sections such as liquid convection heat transfer section, gas-liquid two-phase boiling heat transfer section, liquid lacking section and gas convection heat transfer section. The applicable heat transfer correlations were summarized, and an example calculation was made. The method provided an reference for the similar calculation of gasification heat transfer process.

Available documents

Format PDF

Pages: ICR07-B1-1234

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Study on heat transfer of finned tube heat exchanger for cryogenic liquid.
  • Record ID : 2008-0008
  • Languages: English
  • Source: ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Publication date: 2007/07/21

Links


See other articles from the proceedings (839)
See the conference proceedings