Summary
According to the heat transfer between radiant ceiling unit and surrounding environment, theoretical calculation models of single
piece of the capillary cooling radiant ceiling unit and two units in series combination were set up to calculate their cooling capacities
based on the reasonable simplification of configuration of radiant ceilings. The cooling capacities under the condition of 25°C : room temperature, 15-19°C : supply water temperature were then tested. The comparison between measured data and calculation results show that theoretically calculated cooling capacity of single unit and of two series-connected units agree with the experimental testing data, which shows that the theoretical calculation models are reasonable and feasible and can be used to predict the cooling capacities under real conditions.
Available documents
Format PDF
Pages: 115-118
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: [In Chinese. / En chinois.]
- Record ID : 30011271
- Languages: Chinese
- Source: Journal of Refrigeration - vol. 35 - n. 156
- Publication date: 2014/04
- DOI: http://dx.doi.org/10.3969/j.issn.0253-4339.2014.02.115
Links
See other articles in this issue (13)
See the source
Indexing
- Themes: Comfort air conditioning
- Keywords: Radiation; Cooling capacity; Prediction; Ceiling; Expérimentation; Air conditioning
-
Experimental study on performance of different ...
- Author(s) : ZHANG D., LI C., LI Z.
- Date : 2023/07
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 151
- Formats : PDF
View record
-
Experimental study on a radiant ceiling.
- Author(s) : DI H., WANG W., GE Q., et al.
- Date : 2000/08
- Languages : Chinese
- Source: HV & AC - vol. 30 - n. 135
View record
-
Experimental study of the energy and thermal co...
- Author(s) : FONSECA DIAZ N., CUEVAS C.
- Date : 2011/06
- Languages : English
- Source: HVAC&R Research - vol. 17 - n. 3
View record
-
Vyhodnoceni moznosti vyuziti systému stropniho ...
- Author(s) : LÁCHA D., BASTA J.
- Date : 2007/04
- Languages : Czech
- Source: Vytápení Vetrání Instalace - vol. 16 - n. 4
View record
-
Room air stratification in combined chilled cei...
- Author(s) : SCHIAVON S., BAUMAN F., TULLY B., et al.
- Date : 2012/02
- Languages : English
- Source: HVAC&R Research - vol. 18 - n. 1-2
View record