AIR POLLUTION SOURCES IN VENTILATION SYSTEMS.
Author(s) : PEJTERSEN J.
Summary
POLLUTION SOURCES IN VENTILATION SYSTEMS OF 8 OFFICE BUILDINGS HAVE BEEN STUDIED. THE AIR QUALITY BEFORE AND AFTER EACH COMPONENT IN THE VENTILATION SYSTEM WAS EVALUATED IN DECIPOL BY A PANEL OF TRAINED JUDGES. THE PERCEIVED AIR POLLUTION INCREASED ON AVERAGE 0.8 DECIPOL AS THE AIR PASSED THROUGH THE VENTILATION SYSTEM (EXCLUDING DUCTS). IN THE INVESTIGATED VENTILATION SYSTEMS, THE FILTERS, THE ROTARY HEAT EXCHANGERS AND THE HUMIDIFIERS CONTRIBUTED TO THE POLLUTION OF THE AIR.
Details
- Original title: AIR POLLUTION SOURCES IN VENTILATION SYSTEMS.
- Record ID : 1990-1601
- Languages: English
- Publication date: 1989/08/01
- Source: Source: CLIMA 2000, Sarajevo
vol. 3; 139-144; 3 fig.; 2 tabl.; 4 ref. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Indoor air quality
- Keywords: Office; Building; Ventilation; Air quality; Pollution; Air conditioning
-
INSTALLATIONS DE CLIMATISATION A UNITES TERMINA...
- Author(s) : ADAM J.
- Date : 1990
- Languages : French
- Source: La revue pratique du froid et du conditionnement d'air - vol. 45 - n. 700
View record
-
Ventilation and air quality in office buildings.
- Author(s) : VALBJORN O.
- Date : 1995
- Languages : Danish
- Source: TFVVS Danvak - vol. 31 - n. 4
View record
-
Decreased ventilation requirement through contr...
- Author(s) : FANGER P. O.
- Date : 1991/05
- Languages : English
View record
-
BILAN DES ETUDES DE CONTAMINANTS CHIMIQUES, DE ...
- Author(s) : GOYER N.
- Date : 1989
- Languages : French
- Source: IRSST, Etudes tech./Bilan Connaiss. - 37 p.; fig.; ref.
View record
-
Computer simulation of ventilation strategies f...
- Author(s) : SAID M. N. A., PLETT E. G., SHAW C. Y., VACULIK F.
- Date : 1995/01
- Languages : English
- Source: ASHRAE Transactions.
View record