IIR document

Ammonia evaporation in a mixed configuration chevron plate heat exchanger with and without miscible oil.

Author(s) : KHAN T. S., KHAN M. S., CHYU M. C., et al.

Type of article: Article, IJR article

Summary

An experimental study was conducted to determine the effects of miscible lubricant oil on evaporation of ammonia in a vertical chevron plate heat exchanger. The heat exchanger was configured in a U-type counter flow arrangement with mixed (30°/60°) chevron plate configuration. Experiments were carried out for four saturation temperatures ranging from -25 °C to -2 °C for a fixed ammonia mass flux rate of 6.5 kg m-2 s-1 and over a range of heat flux levels resulting in a vapor quality at the heat exchanger exit ranging between 0.5 and 0.9. For a given saturation temperature, experiments were performed for 0%, 3%, 6% and 9% oil concentrations, by volume in ammonia. The oil concentration, exit vapor quality, heat flux and saturation temperature were found to have significant effects on the heat transfer coefficient and pressure drop of ammonia. Based on the experimental data, correlations to estimate two phase Nusselt number and friction factor, generalized for the whole range of oil concentration have been presented.

Available documents

Format PDF

Pages: 120-134

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Ammonia evaporation in a mixed configuration chevron plate heat exchanger with and without miscible oil.
  • Record ID : 30013518
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 51
  • Publication date: 2015/03

Links


See other articles in this issue (17)
See the source