Analysis on the Effect of Obstruction on Sprinkler Skipping in Air Conditioner Room Fire.
Author(s) : KIM J. T., NAM J. S., KIM R. H., KIM S. Y., RYOU H. S.
Type of article: Periodical article
Summary
Sprinkler skipping is an important issue in fire spread. In general, two sprinklers are installed in air conditioner rooms at the ceiling and 30 cm below to avoid spray failure by energy recovery ventilator in the ceiling. However, there is a problem in that sprinkler skipping occurs in the air conditioner room. In this study, the sprinkler skipping phenomenon was analyzed through numerical analysis and the applicability of the open type of sprinkler operation method was reviewed. As a result, when the upper sprinkler works, sprinkler skipping occurred in all cases. The lower sprinkler shall not rise above the operating temperature of 68.3 °C with a maximum temperature of 65 °C. In particular, the spray failure caused by the energy recovery ventilator reduces the sprinkler head temperature by more than 8 °C by concentrating the spray droplets. As an open type, simultaneous operation of two sprinklers is capable of obtaining an appropriate fire extinguishing effect by covering the fire source with the spray of the lower sprinkler. The research results are expected to help in fire protection in buildings such as modern apartments with air-conditioned rooms.
Available documents
Format PDF
Pages: 11 p.
Available
Free
Details
- Original title: Analysis on the Effect of Obstruction on Sprinkler Skipping in Air Conditioner Room Fire.
- Record ID : 30030520
- Languages: English
- Subject: Technology
- Source: Energies - vol. 15 - n. 18
- Publishers: MDPI
- Publication date: 2022/09
- DOI: http://dx.doi.org/10.3390/en15186776
Links
See other articles in this issue (7)
See the source
Indexing
- Themes: Air conditioning: general information
- Keywords: Safety; Condenser; Fire; Air conditioning; Simulation; Calculation; Residential building
-
A toolkit for primary HVAC system energy calcul...
- Author(s) : BOURDOUXHE J. P. H., GRODENT M., LEBRUN J. J., SAAVEDRA C., SILVA K. L.
- Date : 1994
- Languages : English
- Source: ASHRAE Transactions 1994.
View record
-
COMPUTER-AIDED SIMULATION OF THE AIR CONDITIONI...
- Author(s) : CIESLAKIEWICZ W. F.
- Date : 1986/04/14
- Languages : English
View record
-
Characteristics of buoyancy-driven interzonal a...
- Author(s) : RIFFAT S. B., SHAO L.
- Date : 1995
- Languages : English
- Source: Build. Serv. Eng. Res. Technol. - vol. 16 - n. 3
View record
-
Computational fluid dynamics for studying air m...
- Author(s) : CAFARO E., FRACASTORO G. V.
- Date : 1992/12
- Languages : Italian
- Source: Cond. Aria - vol. 36 - n. 12
View record
-
DISTRIBUTION OF INFILTRATION LOAD OF TALL BUILD...
- Author(s) : ZHAO H.
- Date : 1989/08/01
- Languages : English
View record