Boiling heat transfer and pressure drop of R410A and R134a in horizontal minichannels.

Author(s) : PAMITRAN A. S., CHOI K. I., OH J. T., et al.

Summary

Experimental study on two-phase flow boiling heat transfer of R410A and R134a in horizontal small tubes was reported. The pressure drop and local heat transfer coefficients were obtained over heat flux range of 5 to 40 kW/m2, mass flux range of 70 to 600 kg/m2.s, saturation temperature range of 2 to 12°C, and quality up to 1.0. The test section was made of stainless steel tube with inner tube diameters of 0.5 and 3.0 mm, and lengths of 0.33, 2.0 and 3.0 m. The section was heated uniformly by applying an electric current to the tube directly. The effects on pressure drop and heat transfer coefficient of mass flux, heat flux, tube diameter, and saturation temperature were shown. The experimental results were compared against several existing correlations. A new boiling heat transfer coefficient correlation based on the superposition model for refrigerants in small tubes was developed.

Available documents

Format PDF

Pages: 202-207

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Boiling heat transfer and pressure drop of R410A and R134a in horizontal minichannels.
  • Record ID : 2009-1481
  • Languages: English
  • Source: ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
  • Publication date: 2009/05/20

Links


See other articles from the proceedings (102)
See the conference proceedings