Climespace in the second arrondissement (district) of Paris.
Climespace dans le 2e arrondissement de Paris.
Type of article: Article
Summary
This article concerns a network of chilled water used in air conditioning in Paris. A thermal storage plant using chilled water is described. The capacity of the reservoir provides the equivalent of 17.5 megawatts of refrigeration production over a 6-hour period and eliminates all unpleasant production-related aspects. The reservoir comprises 13 compartments of equal size (each with a volume of 1000 m3), one of which is empty at any given time, thus preventing mixing of chilled and hot fluids.
Details
- Original title: Climespace dans le 2e arrondissement de Paris.
- Record ID : 1998-2509
- Languages: French
- Source: Climespace Info - n. 3
- Publication date: 1997/01
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
Indexing
-
Première mondiale : 12 000 m3 d'eau glacée au s...
- Author(s) : PISANI S.
- Date : 1999/10
- Languages : French
- Source: La revue pratique du froid et du conditionnement d'air - n. 874
View record
-
Stockage de froid : climatisation urbaine à Lyon.
- Author(s) : LUCAS J.
- Date : 1995/10
- Languages : French
- Source: Rev. gén. Froid - vol. 85 - n. 957
View record
-
Distribution urbaine de climatisation par eau g...
- Author(s) : LUCAS J.
- Date : 1994/07
- Languages : French
- Source: Rev. gén. Froid - vol. 84 - n. 945
View record
-
Bilan de 8 années d'expériences de stockage fro...
- Author(s) : AMIEL M.
- Date : 1995/12
- Languages : French
- Source: Chaud Froid Plomb./Chauff. Vent. Cond. - n. 12
View record
-
District cooling re-invented.
- Author(s) : FIORINO D. P.
- Date : 1994/05
- Languages : English
- Source: ASHRAE Journal - vol. 36 - n. 5
View record