COMPARING THE SAVINGS IN ENERGY AND ENERGY COST IN VENTILATION SYSTEMS BY ENERGY RECOVERY WITH REGENERATIVE HEAT AND ENTHALPY EXCHANGERS.

[In German. / En allemand.]

Author(s) : HUBNER H.

Type of article: Article

Summary

THE DEGREE OF HUMIDITY TRANSFER OF HEAT REGENERATORS AS A FUNCTION OF THE UNDERRUN DEW POINT WAS EXPERIMENTALLY DETERMINED AT FIRST. ENERGY CONSUMPTION AND COST OF AIR-CONDITIONING SYSTEMS WITH ENERGY RECOVERY BY HEAT AND ENTHALPY REGENERATORS WERE CALCULATED AND COMPARED IN A VARIANT CALCULATION FOR SIX REAL AND TYPICAL APPLICATIONS OF ENTHALPY REGENERATORS. THE RESULTS REVEAL MAJOR ADDITIONAL SAVINGS IN THERMAL ENERGY AND ENERGY COST OF THE AIR-CONDITIONING SYSTEMS WITH ENTHALPY REGENERATORS. THEY ARE 30-40% AND 15-30%, RESPECTIVELY REFERRED TO THE CONSUMPTION FIGURES AND COST OF THE VARIANT WITH HEAT REGENERATORS.

Details

  • Original title: [In German. / En allemand.]
  • Record ID : 1987-1991
  • Languages: German
  • Publication date: 1986
  • Source: Source: Luft Kältetech.
    vol. 22; n. 3; 123-126; 4 fig.; 6 tabl.; 2 ref.