IIR document

Component-based, gray-box modeling of ductless multi-split heat pump systems.

Author(s) : CHEUNG H., BRAUN J. E.

Type of article: Article, IJR article

Summary

Multi-split ductless heat pumps are touted as an energy efficient option for air conditioning and heating in residential and small commercial applications. However, their use of multiple indoor units with variable speed compressor and fans and complicated controls leads to difficulties in understanding their characteristics by experiments only. A method to model the system using gray-box component models and an empirical control algorithm is described in this paper. The model was constructed from experimental results of an 8 kW R410A dual-unit ductless heat pump system having an accumulator. Strategies for modeling systems with accumulators and saturated control inputs are presented. Parametric studies with varying indoor air temperature, individual indoor unit load ratio, indoor fan speed and total indoor load were conducted. The results show that the model predicts system performance accurately and can help to understand the effect of saturated control inputs and changes of accumulator status on system performance.

Available documents

Format PDF

Pages: 30-45

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Component-based, gray-box modeling of ductless multi-split heat pump systems.
  • Record ID : 30010346
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 38
  • Publication date: 2014/02

Links


See other articles in this issue (34)
See the source