IIR document
Conversion of turbocompressor cooling station with R12 to the station with absorption cooling.
Author(s) : PARÍZEK J., BLUMENTRITT M.
Summary
The cooling station of the Temelin nuclear power station (2 x 1000 megawatts of electric power output) in the Czech Republic, used for air conditioning purposes, was operated using 5 centrifugal chiller units employing R12 as a refrigerant. Therefore it was necessary to look for the replacement either for the refrigerant or refrigerating unit. Different proposals were considered. After evaluation of individual variants, it was decided to replace the existing refrigerating units by absorption water chillers, working with water as refrigerant and solution of lithium bromide and water as absorption medium. For the conversion of the cooling station, the basic requirement was set to utilize at maximum extent the existing equipment. The equipment had to be supplemented by a new working medium, i.e. by hot water system serving as heating medium. The new plant is fully described.
Available documents
Format PDF
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Conversion of turbocompressor cooling station with R12 to the station with absorption cooling.
- Record ID : 2000-1545
- Languages: English
- Source: 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
- Publication date: 1999/09/19
Links
See other articles from the proceedings (447)
See the conference proceedings
-
Conversion of a turbocompressor cooling station...
- Author(s) : PARÍZEK J., BLUMENTRITT M.
- Date : 1999/09/01
- Languages : English
- Source: Compressors '99. The almanac of proceedings from the conference.
View record
-
ADVANTAGES AND LIMITATIONS OF THE THORP METHOD ...
- Author(s) : BAILEY-MCEWAN M.
- Date : 1990/04/23
- Languages : English
View record
-
Liquid cooling architectures for computer syste...
- Author(s) : ELLSWORTH M. J., SCHMIDT R. R.
- Date : 2007/06/23
- Languages : English
- Source: ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
View record
-
Energy conservation effect of heat source syste...
- Author(s) : UEDA K., HASEGAWA Y., SEKI W., et al.
- Date : 2008/05/20
- Languages : English
- Source: 9th IEA Heat Pump Conference 2008: advances and prospects in technology, applications and markets. Conference proceedings [CD-ROM + abstracts].
View record
-
A COMPARISON OF COOLING THERMAL STORAGE AND GAS...
- Author(s) : NEUMAN V. A., SAJED F., GUVEN H. M.
- Date : 1988
- Languages : English
View record