IIR document

Development of a vapour compression cycle with a solution circuit and desorber/absorber heat exchange.

Author(s) : ZHOU Q., RADERMACHER R.

Type of article: Article, IJR article

Summary

A vapour compression cycle with a solution circuit and desorber/absorber heat exchange was investigated experimentally using the ammonia-water mixture. A breadboard heat pump was designed and built to measure the cycle performance. The cooling capacities were between 7 and 12 kilowatts, which increased with an increase of the ammonia concentration. The pressure ratios encountered were in the range of 2-6. A COP of 1.44 at the temperature lift of 79 deg C was recorded with a cooling capacity at 10.25 kilowatts. The experimental results are compared to that of the single-sage and two-stage cycle. The experimental results showed that the COP varied in the range of 1-2%, while the temperature lift increased by the range between 0 and 6 deg C. In addition, the analysis of the test result uncertainties was made.

Available documents

Format PDF

Pages: 85-95

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Development of a vapour compression cycle with a solution circuit and desorber/absorber heat exchange.
  • Record ID : 1997-2807
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 20 - n. 2
  • Publication date: 1997/03

Links


See other articles in this issue (6)
See the source