IIR document

Experimental investigation of a new combined refrigeration system.

Author(s) : GOUDARZI K., MOUSAVI M. R.

Type of article: IJR article

Summary

In this paper, experimental study has been performed to investigate the performance of a new combined cooling system (CCS) included indirect evaporative cooler and 4-bed solar adsorption cooling system. Solar adsorption cooling system acted as pre-cooling for the CCS. in this study, two mass flow rates passing from evaporator of 0.1 and 0.15 kg s−1, and also three volumetric air flow rates passing from indirect evaporative cooler of 700, 850 and 1000 m3 h−1, were investigated. Results were shown that, the highest average efficiency was 104% and obtained for minimum of mass flow passing from solar adsorption cooling system (0.1 kg s−1) and minimum of volumetric air passing from indirect evaporative coolind system (700 m3 h−1). Also, the average efficiency of combined cooling was in the range of 84–104%.

Available documents

Format PDF

Pages: 312-319

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental investigation of a new combined refrigeration system.
  • Record ID : 30029357
  • Languages: English
  • Subject: Technology
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 134
  • Publication date: 2022/02
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2021.11.009
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (29)
See the source