Summary
A novel frost-free air-source heat pump water heater applying dehumidification device and thermal storage on the basis of traditional system is studied in this paper. The operation mode of this system includes heating mode and regeneration mode. An experimental apparatus is built up to study this system, and according to the experiment,the frost-free operating time of this
system is 32 min, 34 min and 36min respectively when the temperature of air is -3°C, 0°C, 3°C and the relative humidity is
85%. And the temperature is high enough for the regeneration of desiccant, which could keep the heat pump heating water continuously. Besides, the COP of this system at temperature of -3°C and 3°C is 17.9% and 3.4% higher than the reverse cycle defrosting system in the same conditions, which proves that this new system has better performance under low environment temperature.
Available documents
Format PDF
Pages: 85-91
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: [In Chinese. / En chinois.]
- Record ID : 30019675
- Languages: Chinese
- Source: Journal of Refrigeration - vol. 36 - n. 164
- Publication date: 2015/08
- DOI: http://dx.doi.org/10.3969/j.issn.0253-4339.2015.04.085
Links
See other articles in this issue (5)
See the source
-
Thermal analysis of a magnesium oxide/water che...
- Author(s) : KATO Y., TAKAHASHI F., WATANABE A., et al.
- Date : 2001/07
- Languages : English
- Source: Applied Thermal Engineering - vol. 21 - n. 10
View record
-
Experimental research on a novel frost-free air...
- Author(s) : WANG Z., WANG F., ZHENG Y.
- Date : 2015/02
- Languages : Chinese
- Source: Journal of Refrigeration - vol. 36 - n. 161
- Formats : PDF
View record
-
The design of gas hydrate cool storage experime...
- Author(s) : YU P., ZHOU X., LIU F., et al.
- Date : 2007/11
- Languages : Chinese
- Source: Refrigeration, Suppl. - suppl.; 1-5; fig.; 14 ref.
View record
-
TWO ZEOLITE POSSIBILITIES: NIGHT-STORAGE HEATIN...
- Author(s) : MAIER-LAXHUBER P., SCHWARZ J.
- Date : 1991/03
- Languages : German
- Source: INFEL Info - n. 1
View record
-
Performance analysis of an integrated solar bas...
- Author(s) : ABERUUE M. J., BANIASADI E., ZIAEI-RAD M.
- Date : 2017/01/05
- Languages : English
- Source: Applied Thermal Engineering - vol. 110
View record