Summary
A novel frost-free air-source heat pump water heater applying dehumidification device and thermal storage on the basis of traditional system is studied in this paper. The operation mode of this system includes heating mode and regeneration mode. An experimental apparatus is built up to study this system, and according to the experiment,the frost-free operating time of this
system is 32 min, 34 min and 36min respectively when the temperature of air is -3°C, 0°C, 3°C and the relative humidity is
85%. And the temperature is high enough for the regeneration of desiccant, which could keep the heat pump heating water continuously. Besides, the COP of this system at temperature of -3°C and 3°C is 17.9% and 3.4% higher than the reverse cycle defrosting system in the same conditions, which proves that this new system has better performance under low environment temperature.
Available documents
Format PDF
Pages: 85-91
Available
Public price
20 €
Member price*
15 €
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: [In Chinese. / En chinois.]
- Record ID : 30019675
- Languages: Chinese
- Source: Journal of Refrigeration - vol. 36 - n. 164
- Publication date: 2015/08
- DOI: http://dx.doi.org/10.3969/j.issn.0253-4339.2015.04.085
Links
See other articles in this issue (5)
See the source
-
Present and future caloric refrigeration and he...
- Author(s) : KITANOVSKI A., PLAZNIK U., TOMC U., et al.
- Date : 2015/09
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 57
- Formats : PDF
View record
-
TWO ZEOLITE POSSIBILITIES: NIGHT-STORAGE HEATIN...
- Author(s) : MAIER-LAXHUBER P., SCHWARZ J.
- Date : 1991/03
- Languages : German
- Source: INFEL Info - n. 1
View record
-
System modeling of gas engine driven heat pump.
- Author(s) : MAHDEREKAL I., SHEN B., VINEYARD E. A.
- Date : 2012/07/16
- Languages : English
- Source: 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
View record
-
Study on energy-efficiency of desiccant outdoor...
- Author(s) : KAWAMOTO K., CHO W., KOHNO H., et al.
- Date : 2015/08/16
- Languages : English
- Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
View record
-
A heat pump driven and hollow fiber membrane-ba...
- Author(s) : ZHANG N., ZHANG L. Z., XU J. C.
- Date : 2016/07
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 67
- Formats : PDF
View record