Experimental study of a miniature vapor compression refrigeration system with two heat sink evaporators connected in series or in parallel.

Author(s) : HE J., WU Y., CHEN X., et al.

Type of article: Article, IJR article

Summary

A miniature vapor compression refrigeration system included two heat sinks connected in series (indicated as series system) or in parallel (indicated as parallel system) was built. The performance of the series system was studied and compared with that of the parallel system. The results indicate that the largest cooling capacity of the two systems is about 160 W and the optimal refrigerant charge is about 0.6 Mtotal in the miniature vapor compress refrigeration (VCR) system. There is no relation between the optimal refrigerant charge and the arrangement of the heat sinks. The coefficient of performance (COP) of the series system ranged from 1.81 to 3.22, while the COP of the parallel system was in the range of 1.51–2.92 under the cooling capacity of 100 W. The cooling of the heat sink 2 lag behind that of the heat sink 1 in the serial system, while the refrigerant is difficult to equally distribute in the parallel system.

Available documents

Format PDF

Pages: 28-35

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental study of a miniature vapor compression refrigeration system with two heat sink evaporators connected in series or in parallel.
  • Record ID : 30012895
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 49
  • Publication date: 2015/01

Links


See other articles in this issue (18)
See the source