Filter collection efficiency and growth of microorganisms on filters loaded with outdoor air.
Author(s) : KEMP S. J., KUEHN T. H., PUI D. Y. H., VESLEY D., STREIFEL A. J.
Summary
A laboratory setup was used to challenge a glass fiber media filter, a polymer fiber media filter, and a two-stage electrostatic precipitator (electronic air cleaner) with 100% ambient outside air for one year. Over the year, fractional efficiency measurements were made as well as microbial sampling to determine filter effectiveness on ambient viable bioaerosols. Both of the media filters demontrated greater than 90% effectiveness on fungi and bacteria bioaerosols. The electrostatic precipitator demonstrated initial efficiency of 95% or greater, which decreased over time as the device was overloaded.
Details
- Original title: Filter collection efficiency and growth of microorganisms on filters loaded with outdoor air.
- Record ID : 1996-1754
- Languages: English
- Source: ASHRAE Transactions.
- Publication date: 1995/01
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (70)
See the conference proceedings
Indexing
-
Themes:
Other air-conditioning equipment;
Indoor air quality - Keywords: Test rig; Filter; Microbiology; Air quality; Performance; Humidity; Air conditioning
-
Growth of microorganisms on HVAC filters under ...
- Author(s) : KEMP S. J., KUEHN T. H., PUI D. Y. H., VESLEY D., STREIFEL A. J.
- Date : 1995/01
- Languages : English
- Source: ASHRAE Transactions.
View record
-
Activated carbon filters for use in ventilation...
- Author(s) : HOLMBERG R., STRINDEHAG O., TROKELSSON S.
- Date : 1993/11/01
- Languages : English
View record
-
Determine the efficacy of antimicrobial treatme...
- Author(s) : FOARDE K. K., HANLEY J. T.
- Date : 2001
- Languages : English
- Source: ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
View record
-
Development of field test method for ventilatio...
- Author(s) : LEHTIMÄKI M., TAIPALE A.
- Date : 2000/06/04
- Languages : English
- Source: Progress in modern ventilation. Ventilation 2000. Proceedings of the 6th International symposium on ventilation for contaminant control.
View record
-
Verification of cleanliness of HVAC systems.
- Author(s) : PASANEN P.
- Date : 1999/03/24
- Languages : English
View record