Finned small diameter tube heat exchanger.

[In Japanese. / En japonais.]

Author(s) : DANG C., DAIGUJI H., HIHARA E., et al.

Type of article: Article

Summary

The performance of finned small tube heat exchangers was investigated both experimentally and theoretically (diameters 1.0, 2.1 and 4.0 mm). Exchanged heat and pressure drop obtained from numerical simulation agreed well with the experimental ones. Calculation results show that the volume of a 2.0 mm tube heat exchanger can be reduced to 33% of that of a 4 mm tube heat exchanger with the same capacity.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 2003-0680
  • Languages: Japanese
  • Source: Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 18 - n. 2
  • Publication date: 2001
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (4)
See the source