Heat transfer and pressure drop correlations for compact heat exchangers with multi-region louver fins.

Author(s) : LI W., WANG X.

Type of article: Article

Summary

An experimental study on the air-side heat transfer and pressure drop characteristics for brazed aluminium heat exchangers with multi-region louver fins and flat tubes was conducted. A series of tests were conducted for heat exchangers with different numbers of louver regions at the air-side Reynolds numbers of 400-1600 based on the louver pitch. The air-side thermal performance data were analyzed by using the effectiveness-NTU method. The characteristics of the heat transfer and pressure drop for heat exchangers with different geometry parameters were presented in terms of the Colburn j factor and Fanning friction f factor as function of the Reynolds number. [Reprinted with permission from Elsevier. Copyright, 2010].

Details

  • Original title: Heat transfer and pressure drop correlations for compact heat exchangers with multi-region louver fins.
  • Record ID : 2010-1798
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 53 - n. 15-16
  • Publication date: 2010/07
  • DOI: http://dx.doi.org/10.1016/j.ijheatmasstransfer.2010.04.002