HORIZONTAL FLOW BOILING OF PURE AND MIXED REFRIGERANTS.

Author(s) : ROSS H.

Type of article: Article

Summary

THE RESEARCH INVOLVED DETERMINING EXPERIMENTAL HEAT TRANSFER COEFFICIENTS FOR PURE R152A AND R13B1 AND FOR 4 MIXTURES OF THESE REFRIGERANTS. THE MIXTURES YIELDED SHARPLY LOWER HEAT TRANSFER COEFFICIENTS THAN EITHER PURE REFRIGERANT. CORRELATIVE EVIDENCE SUGGESTS THAT FULL SUPPRESSION OF NUCLEATE BOILING IS EASIER TO ACHIEVE WITH MIXTURES THAN PURE FLUIDS. EXISTING CORRELATIONS WERE COMPARED TO THE DATA WITH SUCCESS FOR BOTH PURE AND MIXED FLUIDS.

Details

  • Original title: HORIZONTAL FLOW BOILING OF PURE AND MIXED REFRIGERANTS.
  • Record ID : 1988-0521
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 30 - n. 5
  • Publication date: 1987

Links


See other articles in this issue (4)
See the source