LABORATORY EXAMINATION AND SEASONAL ANALYSES OF THE DYNAMIC LOSSES FOR A CONTINUOUSLY VARIABLE-SPEED HEAT PUMP.
Author(s) : MILLER W. A.
Summary
AN AIR-TO-AIR SPLIT-SYSTEM, CONTINUOUSLY VARIABLE SPEED HEAT PUMP OF NOMINAL 8.8 KILOWATT COOLING CAPACITY WAS INSTRUMENTED AND TESTED IN THE LABORATORY. THE SYSTEM OPERATING CONDITIONS, COP AND SYSTEM CAPACITY WERE MEASURED DURING FROSTING/DEFROSTING TESTS AND DURING BOTH HEATING AND COOLING MODE CYCLING TESTS. FOR FT WORTH (TEX), KNOXVILLE (TENN), AND SYRACUSE (NY), ANALYSIS OF ENERGY COST SAVINGS DUE TO MODULATION JUSTIFY A COST PREMIUM OF $ 400 FOR THREE-YEAR PAYBACK.
Details
- Original title: LABORATORY EXAMINATION AND SEASONAL ANALYSES OF THE DYNAMIC LOSSES FOR A CONTINUOUSLY VARIABLE-SPEED HEAT PUMP.
- Record ID : 1989-2449
- Languages: English
- Publication date: 1988
- Source: Source: ASHRAE Trans.
vol. 94; n. 2; 1246-1268; 12 fig.; 7 tabl.; 14 ref.; discuss. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Heat pumps techniques
- Keywords: Frosting; Variable speed; Inverter; Profitability; Air-air; Heat pump; USA; Defrosting; Compressor
-
Scrollverdichter mit Drehzahlvariation.
- Author(s) : AFJEI T.
- Date : 1993
- Languages : German
View record
-
Conventional defrosting characteristics for var...
- Author(s) : TIAN H., DONG J., YAO Y., et al.
- Date : 2014/03
- Languages : Chinese
- Source: HV & AC - vol. 44 - n. 288
- Formats : PDF
View record
-
INTRODUCING VARIABLE SPEED DRIVES.
- Author(s) : SHELDRAKE A. M.
- Date : 1991/04
- Languages : English
- Source: J. chart. Inst. Build. Serv. - vol. 13 - n. 4
View record
-
Study about the uses of high efficiency centrif...
- Author(s) : UEDA K., HASEGAWA Y., SHIMODA Y.
- Date : 2008/07
- Languages : Japanese
- Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 136
View record
-
MEASURED EFFICIENCY OF VARIABLE-SPEED DRIVES IN...
- Author(s) : RUOHONIEMI T. J.
- Date : 1988
- Languages : English
View record