MANAGEMENT OF CONTAMINATION IN COOLING SYSTEMS FOR SUPERCONDUCTING GENERATORS. 3. IMPURITY CONCENTRATION MEASUREMENTS EVOLVED FROM A SUPERCONDUCTING GENERATOR-HESPER 1.

Author(s) : NITTA T.

Type of article: Article

Summary

BEFORE STARTING THE COOL-DOWN TO 4.2K A PURIFICATION PROCESS MUST BE DONE BY CIRCULATING A HELIUM GAS THROUGH A PURIFIER USING A CRYOGENIC ADSORBER. FOR THE DESIGN OF THIS CRYOGENIC ADSORBER, THERE IS NEEDED TO KNOW THE AMOUNTS OF EVOLVED GAS AND COMPONENTS FROM THE SUPERCONDUCTING GENERATORS. THIS PAPER PRESENTS A NEW METHOD OF ANALYZING TRACE-LEVEL IMPURITIES AND THE TEST RESULTS OF TIME DEPENDENT GAS EVOLVING RATES WITH THE USE OF SUPERCONDUCTING GENERATOR, HESPER 1.

Details

  • Original title: MANAGEMENT OF CONTAMINATION IN COOLING SYSTEMS FOR SUPERCONDUCTING GENERATORS. 3. IMPURITY CONCENTRATION MEASUREMENTS EVOLVED FROM A SUPERCONDUCTING GENERATOR-HESPER 1.
  • Record ID : 1992-0072
  • Languages: English
  • Source: Cryogenics - vol. 30
  • Publication date: 1990/09