Modelling a heat pump operating with CO2.

Modélisation d'une pompe à chaleur fonctionnant avec du CO2.

Author(s) : GUITARI I., HABERSCHILL P., LALLEMAND A.

Type of article: Article

Summary

This study characterizes the behaviour and determines the optimum conditions for operation of compression thermal machines using CO2 as a refrigerant. The results obtained result from a trial run carried out on a CO2 air/water heat pump and from a model simulating its operation. The results show that for a variation in the temperature of the heat source (water) between 20 and 40 °C and a cold source temperature of 5 °C, the optimal discharge pressure varies between 75 and 115 bar.

Details

  • Original title: Modélisation d'une pompe à chaleur fonctionnant avec du CO2.
  • Record ID : 2005-1198
  • Languages: French
  • Source: Rev. gén. Froid - n. 1047
  • Publication date: 2004/10

Links


See other articles in this issue (3)
See the source