Modelling of heat transfer and pressure drop during condensation of a pure refrigerant inside a horizontal smooth tube.

Modélisation du transfert de chaleur et de la perte de charge lors de la condensation d'un frigorigène pur à l'intérieur d'un tube lisse horizontal.

Author(s) : BOUSSETTA A., HALOUANI K., AYADI A., et al.

Type of article: Article

Summary

For pure refrigerants such as HCFC-22, HFC-134a, HFC-125 and HFC-32, results show that the variation in the heat transfer coefficient and in the pressure drop is an increasing function of the vapour mass velocity at tube inlet and of the vapour saturation. These results show good correlation with experimental values found in the literature. An overall mean deviation of 6% is observed for the heat transfer, and of 1% for the pressure drop.

Details

  • Original title: Modélisation du transfert de chaleur et de la perte de charge lors de la condensation d'un frigorigène pur à l'intérieur d'un tube lisse horizontal.
  • Record ID : 2003-1714
  • Languages: French
  • Source: Entropie - vol. 38 - n. 243
  • Publication date: 2002
  • Document available for consultation in the library of the IIR headquarters only.