Oil retention and pressure drop of R134a, R1234yf and R410A with POE 100 in suction lines.

Number: pap. 2508

Author(s) : RAMAKRISHNAN A., HRNJAK P. S.

Summary

An experimental investigation of oil retention and pressure drop characteristics for R1234yf, R134a and R410A with POE 100 is presented, for horizontal and vertical suction lines of 10.2 mm internal diameter. Conditions of operation include a saturation temperature of 13°C and a superheat of 15°C, with the superficial vapor velocity and the oil in circulation ratio both varied in the range of 1-6 m/s and 1-5% respectively. The effect of lubricant viscosity on oil retention and pressure drop is also presented by comparing results with those of POE 32, under the same conditions of operation.

Available documents

Format PDF

Pages: 10 p.

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Oil retention and pressure drop of R134a, R1234yf and R410A with POE 100 in suction lines.
  • Record ID : 30006600
  • Languages: English
  • Source: 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Publication date: 2012/07/16

Links


See other articles from the proceedings (195)