Summary
The article presents an adsorption air cooling system consisting of a honeycomb rotary dehumidifier, a sensible heat exchanger, a heater and two evaporative coolers with water spray. It is operated in ventilation mode. The performance of the cooling system was examined at regeneration air temperature as low as 80 deg C. The amount of enthalpy of about 16.5 kilojoules/kilograms could be reduced from the room with the COP of 61% at the superficial air velocity of 1 meter/second. However, it was found that the COP and cooling capacity significantly depend on the operating conditions; air velocities, rotation speed of the dehumidifier, regeneration temperature and inlet air conditions.
Details
- Original title: Open cycle adsorption cooling system with a thermal swing honeycomb dehumidifier.
- Record ID : 1999-2912
- Languages: English
- Source: Fundamentals of adsorption - FOA6. Proceedings of the Sixth International Conference.
- Publication date: 1998/05/24
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles from the proceedings (9)
See the conference proceedings
-
Experimental investigation of a LiCl-water open...
- Author(s) : GOMMED K., GROSSMAN G., ZIEGLER F.
- Date : 2002/09/24
- Languages : English
- Source: Proceedings of the International Sorption Heat Pump Conference.
View record
-
Optimization of adsorption isotherm taxonomy fo...
- Author(s) : SULTAN M., MIYAZAKI T., SAHA B. B., et al.
- Date : 2015/08/16
- Languages : English
- Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
View record
-
Open-cycle absorption and desiccant technology.
- Author(s) : GROSSMAN G.
- Date : 2011/04/06
- Languages : English
- Source: Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
View record
-
Theoretical analysis of an open-cycle absorptio...
- Author(s) : LAZZARIN R. M., LONGO G. A., GASPARELLA A.
- Date : 1996/03
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 19 - n. 3
- Formats : PDF
View record
-
Parametric study of an energy efficient air con...
- Author(s) : KINSARA A. A., RABGHI O. M. al-, ELSAYED M. M.
- Date : 1998/05
- Languages : English
- Source: Applied Thermal Engineering - vol. 18 - n. 5
View record