OPERATING PERFORMANCE OF A WATER SPRAY ON AN AIR-TYPE CONDENSING UNIT.
Author(s) : GUINN G. R., NOVELL B. J.
Summary
THE SPRAYER IS A SYSTEM TO CONTROL AND DIRECT A FINE MIST OF WATER ONTO THE HEAT TRANSFER SURFACES, THEREBY ENHANCING THE HEAT REJECTION RATE AND IMPROVING OVERALL SYSTEM PERFORMANCE. THE UNIT WAS TESTED OVER A WIDE RANGE OF DRY BULB AND RELATIVE HUMIDITY CONDITIONS OF THE AIR ENTERING THE CONDENSER. THE SPRAY WAS FOUND TO INCREASE THE ENERGY EFFICIENCY RATIO BY 12% TO 19%. THE COMPRESSOR HEAD PRESSURE WAS REDUCED FROM 9% TO 17%.
Details
- Original title: OPERATING PERFORMANCE OF A WATER SPRAY ON AN AIR-TYPE CONDENSING UNIT.
- Record ID : 1984-1141
- Languages: English
- Publication date: 1981
- Source: Source: ASHRAE Trans.
vol. 87; n. 2; 373-381; 4 fig.; 2 tabl. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Spray; Air-cooled exchanger; Performance; Air conditioning; Water
-
Save energy, spray water!
- Author(s) : URE Z.
- Date : 2004/01
- Languages : English
- Source: Refrig. World - n. 1
View record
-
Study of a high efficiency residential split wa...
- Author(s) : HU S. S., HUANG B. J.
- Date : 2005/08
- Languages : English
- Source: Applied Thermal Engineering - vol. 25 - n. 11-12
View record
-
Indirect adiabatic cooling with air washer and ...
- Author(s) : KRAJCÍ Í.
- Date : 2004/09/01
- Languages : English
- Source: Compressors 2004: 5th International Conference on Compressors and Coolants
- Formats : PDF
View record
-
Performance evaluations of refrigeration system...
- Author(s) : HOSOZ M., KILICARSLAN A.
- Date : 2004/06/25
- Languages : English
- Source: Int. J. Energy Res. - vol. 28 - n. 8
View record
-
OPTIMUM CONTROL OF AIR CONDENSER BY AIR HUMIDIF...
- Author(s) : CEJKA Z.
- Date : 1988/05/17
- Languages : English
- Source: Cold chains in economic perspective.
- Formats : PDF
View record