Optimal control and performance test of solar-assisted cooling system.

Author(s) : HUANG B. J., YEN C. W., WU J. H., et al.

Type of article: Article

Summary

The solar-assisted cooling system (SACH) was developed in the present study. The ejector cooling system (ECS) is driven by solar heat and connected in parallel with an inverter-type air conditioner (A/C). The cooling load can be supplied by the ECS when solar energy is available and the input power of the A/C can be reduced. In variable weather, the ECS will probably operate at off-design condition of ejector and the cooling capability of the ECS can be lost completely. In order to make the ejector operate at critical or non-critical double-choking condition to obtain a better performance, an electronic expansion valve was installed in the suction line of the ejector to regulate the opening of the expansion valve to control the evaporator temperature. This will make the SACH always produce cooling effect even at lower solar radiation periods while the ejector performs at off-design conditions. The energy saving of A/C is experimentally shown 50-70% due to the cooling performance of ECS. The long-term performance test results show that the daily energy saving is around 30-70% as compared to the energy consumption of A/C alone (without solar-driven ECS). The total energy saving of A/C is 52% over the entire test period. [Reprinted with permission from Elsevier. Copyright, 2010].

Details

  • Original title: Optimal control and performance test of solar-assisted cooling system.
  • Record ID : 30002170
  • Languages: English
  • Source: Applied Thermal Engineering - vol. 30 - n. 14-15
  • Publication date: 2010/10
  • DOI: http://dx.doi.org/10.1016/j.applthermaleng.2010.06.004

Links


See other articles in this issue (15)
See the source