IIR document

Performance optimization of a large-scale ammonia heat pump in off-design conditions.

Number: pap. 0014

Author(s) : JØRGENSEN P., OMMEN T., MARKUSSEN W. B., et al.

Summary

A thermodynamic model of a 5 MW test and demonstration heat pump, implemented in the district heating network of Copenhagen, is presented. A genetic algorithm was applied to the model for 27 different operating conditions, optimizing the system Coefficient of Performance (COP) by adjusting the available set points (SP) in the heat pump system. Analyzing the optimization result, new SP values depending on the operating conditions were proposed. The potential improvement in COP was between 0.4 % and 2.9 %. A performance map for all operating conditions was presented and discussed. In general the COP increased with decreasing forward temperatures, increasing source temperatures and further an optimum at 80 % heating load was observed within the investigated span of operating conditions.

Available documents

Format PDF

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Performance optimization of a large-scale ammonia heat pump in off-design conditions.
  • Record ID : 30025685
  • Languages: English
  • Source: 8th Conference on Ammonia and CO2 Refrigeration Technology. Proceedings: Ohrid, North Macedonia, Avril 11-13, 2019.
  • Publication date: 2019/04/11
  • DOI: http://dx.doi.org/10.18462/iir.nh3-co2.2019.0014

Links


See other articles from the proceedings (50)
See the conference proceedings