Prediction of forced convective condensation characteristics of new alternatives to R502 inside water/refrigerant enhanced surface tubing.

Author(s) : SAMI S. M., POIRIER B.

Summary

An experimental study on the heat transfer characteristics of two-phase flow condensation of alternative refrigerant mixtures to R502 is presented. The test section was a horizontal, enhanced surface tubing in a water-to-refrigerant heat exchanger setup. Correlations were proposed to predict condensation heat transfer characteristics. For R404A, R507, R408A, and a quaternary blend, R32/R125/R143a/R134a, the proposed correlations predicted the heat transfer characteristics with a deviation of less than more or less 20%.

Details

  • Original title: Prediction of forced convective condensation characteristics of new alternatives to R502 inside water/refrigerant enhanced surface tubing.
  • Record ID : 1999-2834
  • Languages: English
  • Source: ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
  • Publication date: 1998
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (79)
See the conference proceedings