PRESSURE DROP OF SUBCOOLED FLOW BOILING IN NARROW TUBE.

[In Japanese. / En japonais.]

Author(s) : INASAKA F., NARIAI N., SHIMURA T.

Type of article: Article

Summary

EXPERIMENTS WERE CONDUCTED AT NEARLY AMBIENT PRESSURE UNDER THE CONDITIONS: TUBE INSIDE DIAMETER: 1 AND 3 MILLIMETERS, TUBE LENGTH: 10 TO 100 MM, WATER MASS VELOCITY: 7,000 TO 20,000 KG/M2 S. THE FRICTION PRESSURE DROP RATIO OF SUBCOOLED FLOW BOILING TO NON-HEATING WATER FLOW WAS EXAMINED BY INCREASING THE HEAT FLUX. THE RATIO BEGINS TO INCREASE AT THE HEAT FLUX PROPOSED BY THE SAHA-ZUBER CORRELATION. THE RATIO WAS FURTHER COMPARED WITH THE BERGLES-DORMER CORRELATION. THE TWO-PHASE FRICTION MULTIPLIER OF SUBCOOLED FLOW BOILING WAS EXAMINED ASSUMING THE AHMAD VOID FRACTION AND APPLIE OTE LOCKHART-MARTINELLI CORRELATION. THE ABNORMARITY OF THE SUBCOOLED FLOW BOILING IN 1 MM INSIDE DIAMETER TUBE WAS CONFIRMED. (JSME INT. J., SER. II, JP., 31, N 2, 1988/05, 349.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 1989-0867
  • Languages: Japanese
  • Source: Trans. JSME, B - vol. 53 - n. 494.
  • Publication date: 1988
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (5)
See the source