Range of application of displacement, source and mixed flows, with or without cooled ceilings.
Anwendungsbereiche von Verdrängungs-, Quelluft- und Misch- strömung in Kombination mit Deckenkühlung.
Author(s) : FITZNER K.
Type of article: Article
Summary
Preventing draughts requires a limit of 100 watts/m2 when using mixed flow or cooled ceilings. Source (displacement) flow with air supplied across the entire floor has no such limitation. There is also no limitation for (real or unidirectional) displacement flow from the ceiling or from the floor, as long as the flow pattern is stable. An additional relative cooling capacity of the cooled ceiling up to 100 watts/m2 is possible, though usually not necessary. Source flow from the side walls is limited to 600 watts/m2, depending on the lenght of the outlet. For higher capacities cooled ceilings can be of use.
Details
- Original title: Anwendungsbereiche von Verdrängungs-, Quelluft- und Misch- strömung in Kombination mit Deckenkühlung.
- Record ID : 1998-1183
- Languages: German
- Source: KI Luft Kältetech. - vol. 33 - n. 3
- Publication date: 1997/03
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (4)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Velocity (fluids, gases); Radiation; Floor; Ventilation; Air; Ceiling; Optimization; Flow rate; Air conditioning; Air distribution
-
Studies on a pressurized type underfloor air-co...
- Author(s) : TAKAHASHI A., KONG C. N., NAKATANI H., OHWASE S.
- Date : 1996
- Languages : Japanese
- Source: Trans. JAR - vol. 13 - n. 2
View record
-
Sensation de courant d'air : l'élément fondamen...
- Author(s) : CADIERGUES R.
- Date : 2004/01
- Languages : French
- Source: CVC - n. 827
View record
-
Velocity distribution in a room ventilated by d...
- Author(s) : NIELSEN P. V.
- Date : 2000/04
- Languages : English
- Source: Energy Build. - vol. 31 - n. 3
View record
-
I collaudi degli impianti aeraulici a fini di b...
- Author(s) : CATTANEO P., NOCERA U., SILVESTRI M.
- Date : 1999/09
- Languages : Italian
- Source: Cond. Aria - vol. 43 - n. 9
View record
-
Temperature field measurement around the room a...
- Author(s) : AN K. H., LEE I. S.
- Date : 2000/11
- Languages : English
- Source: JSME int. J., B - vol. 43 - n. 4
View record