SAVING ENERGY AND MONEY BY CHILLED WATER STORAGE.

Author(s) : ROBA H. A., NOEL G.

Summary

AT THE HEAD-OFFICE (83,000 M2 ), OF AN INSURANCE COMPANY AN EXPANSION AREA OF 42,000 M2 WILL BE AD THE TOTAL PEAK COOLING LOAD OF THE EXISTING BUILDING (3.6 MW) AND OF THE NEW BUILDING (2.7 MW) IS 6.3 MW. TO THE EXISTING COOLING PLANT (3 X 1.9 MW CENTRIFUGAL), A NEW COOLING PLANT (2 X 0. 65 MW RECIPROCAL) AND A CHILLED WATER STORAGE OF 1,500 M3 WITH FLOATING MEMBRANE WILL BE ADDED. IT IS INTENDED TO RUN SOME CHILLERS DURING THE NIGHT. THE SAVING OF ENERGY RESULTS OF THE GOOD EFFICIENCY OF THE CHILLERS WORKING AT THEIR NOMINAL CAPACITY WITH GOOD CONDENSING CONDITIONS.

Details

  • Original title: SAVING ENERGY AND MONEY BY CHILLED WATER STORAGE.
  • Record ID : 1987-1985
  • Languages: English
  • Subject: Environment
  • Publication date: 1986/11/05
  • Source: Source: Proc. 1st eur. Symp. Air Cond. Refrig., Brussels
    11-18; 5 fig.; 1 tabl.
  • Document available for consultation in the library of the IIR headquarters only.