SELECTION OF THE RATIONAL PARAMETERS OF PIPINGS FOR HEATING COLD STORE FLOORS.

[In Russian. / En russe.]

Author(s) : KURYLEV E. S., EGLIT A. Ja., MIRONOVA A. N.

Type of article: Article

Summary

A RELATIONSHIP WAS ESTABLISHED BETWEEN THE OPTIMUM SPACING OF THE PIPES OF THE PIPING NETWORK FOR HEATING COLD STORE FLOORS WITH A HOT LIQUID, THE OPTIMUM THICKNESS OF FLOOR INSULATION AND THE PIPE DIAMETER AND MATERIAL, THE TYPE OF INSULATING MATERIAL, THE ROOM TEMPERATURE AND THE TYPE OF PACKAGING OF PRODUCTS. THE AUTHORS NOTE THAT INSTEAD OF THE USUAL SPACING OF 0.8-1.2 M, THE OPTIMUM SPACING MAY BE GREATER THAN 2 M, ACCORDING TO THE CHARACTERISTICS OF THE SITE.

Details

  • Original title: [In Russian. / En russe.]
  • Record ID : 1986-1550
  • Languages: Russian
  • Source: Kholodilnaya Tekhnika - n. 4
  • Publication date: 1985
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (141)
See the source