METHODS TO SHORTEN THE DEFROST TIME HAVE BEEN CARRIED OUT ON A 0.75 KILOW HEAT PUMP AND THE ENERGY BALANCE DURING DEFROSTING HAS BEEN ANALYZED. THE FOLLOWING METHODS ARE EFFECTIVE IN SHORTENING THE DEFROST TIME: 1) INCREASING THE POWER INPUT TO THE COMPRESSOR DURING DEFROSTING ; 2) UTILIZING THE COMPRESSOR FOR THERMAL ENERGY STORAGE ; 3) REDUCING THE WATER LEFT IN THE OUTDOOR HEAT EXCHANGER FINS. A HEAT PUMP WITH THE NEW DEFROSTING SYSTEM WAS TESTED AND ITS DEFROST TIME WAS 1 MIN 55 S AS COMPARED WITH THE DEFROST TIME OF A CONVENTIONAL HEAT PUMP OF ABOUT 4 TO 5 MIN.