STUDIES ON PREVENTION OF MIXING ENERGY LOSS IN AIR-CONDITIONED ROOM. 3. EFFECTS OF TYPE OF INTERIOR AIR OUTLET AND HEAT STORAGE LOAD ON ENERGY LOSS, AND PROPERTY OF ROOM AIR TEMPERATURE DISTRIBUTION.

[In Japanese. / En japonais.]

Author(s) : ITO H., NAKAHARA N.

Type of article: Article

Summary

THE PURPOSES OF THE STUDY ARE TO DISCLOSE THE MECHANISM OF THE ENERGY LOSS AND TO ESTABLISH THE OPTIMUM DESIGN METHODS OF AIR-DIFFUSION DEVICES AND THE CONTROL DEVICES IN THE SIMULTANEOUS HEATING AND COOLING SYSTEM. THE RESULTS ARE SUMMARIZED AS FOLLOWS: 1) THE TYPES OF INTERIOR OUTLETS INVESTIGATED ARE THE ANEMOSTAT DIFFUSER, RADIAL-FLOW OUTLET AND RECTANGULAR GRILL. THE GRILL MOUNTED ON THE HIGH SIDEWALL BROUGHT THE LARGEST AMOUNT OF ENERGY LOSS ; 2) IT WAS CONFIRMED THAT THE CONTROL-TEMPERATURE DIFFERENCE BETWEEN THE PERIMETER AND THE INTERIOR HAD THE GREATEST INFLUENCE ON ENERGY LOSS ; 3) THE HEAT STORAGE LOAD IN THE FLOOR SLAB HAD ALMOST NO EFFECT ON ENERGY LOSS, BUT IT HAS GREAT INFLUENCE ON THE THERMAL COMFORT OF OCCUPANTS ; 4) AMONG LOCATIONS OF THE PERIMETER THERMOSTAT, THE FRONT POSITION OF THE FAN-COIL UNIT BROUGHT THE MOST DESIRABLE EFFECTS AND THE INLET POSITION OF THE FAN-COIL UNIT BROUGHT THE MOST DISADVANTAGEOUS EFFECTS ON ENERGY LOSS RIBUTION.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 1990-2576
  • Languages: Japanese
  • Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 41
  • Publication date: 1989/10