System for hot water supply by a heat pump that recovers heat from daily waste water. 1. Research on the actual conditions of waste water.

[In Japanese. / En japonais.]

Author(s) : UKAJI M., NIHEI T., ITHO H.

Type of article: Article

Summary

For the purpose of obtaining fundamental data required for the designing of a heat pump system, the quantity and temperature of water for various uses were studied in two hotels and residential houses. It was found that the temperature of waste water from the guest rooms was higher than 30 deg C yearround and that the most calories (70 to about 90 %) used to heat the water remained in the waste water, making it an adequate heat source for the heat pump.

Details

  • Original title: [In Japanese. / En japonais.]
  • Record ID : 1994-1202
  • Languages: Japanese
  • Source: Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 51
  • Publication date: 1993/02
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (7)
See the source