THE PERFORMANCE OF COILED FINNED-TUBE HEAT EXCHANGER SUBMERGED IN A HOT-WATER STORE: THE EFFECT OF THE EXCHANGER'S ORIENTATION.

Author(s) : MOTE R., PROBERT S. D., NEVRALA D.

Type of article: Article

Summary

A COILED-PIPE EXCHANGER WAS EMPLOYED TO EXTRACT HEAT RAPIDLY AT RELATIVELY HIGH TEMPERATURE FROM A HOT-WATER CHARGED TANK. FOR THE HEAT-EXCHANGER ORIENTATIONS TESTED, THE MAXIMUM EFFECTIVENESS, WITH RESPECT TO THE QUALITY OF THE HEAT EXTRACTED WAS ACHIEVED BY HAVING THE AXIS OF THE COILED HEAT-EXCHANGER ARRANGED HORIZONTALLY WITH ITS INLET AT THE LOWEST LEVEL, AND WITH THE LOWER RATE TESTED OF WATER BEING PASSED THROUGH THE HEAT-EXCHANGER'S PIPE, PARTLY BECAUSE THIS LED TO A LOWER RATE OF DISRUPTION OF THE STRATIFICATION OF THE WATER WITHIN THE STORE. (PASCAL, Bibliogr. int. , ENERG., FR., N 4, 1991, 2844.

Details

  • Original title: THE PERFORMANCE OF COILED FINNED-TUBE HEAT EXCHANGER SUBMERGED IN A HOT-WATER STORE: THE EFFECT OF THE EXCHANGER'S ORIENTATION.
  • Record ID : 1992-0145
  • Languages: English
  • Source: Appl. Energy - vol. 38 - n. 1
  • Publication date: 1991

Links


See other articles in this issue (1)
See the source

Indexing