A METHOD FOR DETERMINATION OF REFRIGERANT LOSSES FROM REFRIGERATORS.
[In Czech. / En tchèque.]
Author(s) : ZELINGER Z.
Type of article: Article
Summary
A METHOD FOR THE MEASUREMENT OF REFRIGERANT LOSSES FROM REFRIGERATOR UNIT BY INTEGRAL TEST IS BASED ON THE DETERMINATION OF THE LINEAR INCREASE OF THE COOLING AGENT CONCENTRATION ON TIME. TESTED REFRIGERATOR UNIT IS PLACED INTO A SPECIAL CHAMBER. REFRIGERANT LEAKS FROM THE UNIT INTO THE MEASURING CHAMBER, WHEREFROM IT FLOWS VIA A CLOSED CIRCUIT TO A SENSITIVE DETECTOR. THE VALUE OF THE SLOPE OF DEPENDENCE MEASURED IS RELATED TO THE MAGNITUDE OF THE LEAKAGE. PERMEATION TUBES WERE USED AS STANDARDS FOR CALIBRATION OF R11 AND R12 CONCENTRATIONS.
Details
- Original title: [In Czech. / En tchèque.]
- Record ID : 1989-2268
- Languages: Czech
- Source: Prum. Potravin - vol. 40 - n. 1
- Publication date: 1989
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
Indexing
-
Themes:
CFCs;
Supermarkets, display cabinets;
Containment, refrigerant charge reduction - Keywords: Halogen; Measurement; Maintenance; R12; R11; Leakage; Refrigerant
-
An investigation of refrigerant leakage in comm...
- Author(s) : FRANCIS C., MAIDMENT G., DAVIES G.
- Date : 2017/02
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 74
- Formats : PDF
View record
-
AVOIDANCE OF CFC EMISSIONS FROM LOW AND MEDIUM ...
- Author(s) : GEHRLEIN K., RECKNAGEL J., TRABER R.
- Date : 1989
- Languages : German
- Source: Klima Kälte Heiz. - vol. 17 - n. 7-8
View record
-
REPLACEMENT OF CFCS FROM REFRIGERATION UNITS.
- Author(s) : LANDE A. van der
- Date : 1989/07
- Languages : Dutch
- Source: Koude Klim. - vol. 82 - n. 7
View record
-
Refrigerants' recovery.
- Author(s) : IWAMOTO T.
- Date : 2000/10
- Languages : Japanese
- Source: Refrigeration - vol. 75 - n. 876
View record
-
Condensing unit and display case.
- Author(s) : SEYAMA Y., SASAKI H.
- Date : 1997/05
- Languages : Japanese
- Source: Refrigeration - vol. 72 - n. 835