A WATER HEATER RECOVERING ENERGY FROM REFRIGERATING PLANT.

CHAUFFE-EAU RECUPERANT L'ENERGIE DES INSTALLATIONS FRIGORIFIQUES.

Author(s) : RIDEL P.

Type of article: Article

Summary

DESCRIPTION OF A HEATING UNIT FOR DOMESTIC WATER AT ABOUT 318-328 K (45 TO 55 DEG C) RECOVERING THE DESUPERHEATING HEAT-FROM THE HIGH PRESSURE VAPOURS OF A REFRIGERATING PLANT (I.E. 10 TO 20% OF CONDENSER CAPACITY). IN PRACTICE, STORAGE SHOULD BE PROVIDED FOR ONE DAY OPERATION IF THE DAILY OPERATING TIME IS ABOUT 16 HRS. THE A.DESCRIBES THE CASE OF HEAT RECOVERY FROM DISPLAY CASES IN A SUPERMARKET AND ESTIMATES THAT THE AMORTISATION TIME IS ABOUT FOUR YEARS. A.G.

Details

  • Original title: CHAUFFE-EAU RECUPERANT L'ENERGIE DES INSTALLATIONS FRIGORIFIQUES.
  • Record ID : 1982-0996
  • Languages: French
  • Source: La revue pratique du froid et du conditionnement d'air - vol. 36 - n. 510
  • Publication date: 1981
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (1)
See the source