The paper presents an experimental investigation of a novel H2O/LiBr absorption refrigerator that employs a steam ejector to recover the heat otherwise wasted in conventional H2O/LiBr systems to enhance the concentration process. In the system, the ejector entrains the vapour evolved from the concentration process and compresses so that it can be re-used for the concentration process. Compared with double-effect H2O/LiBr system, this refrigerator is simple and low cost. In using high temperature heat sources, this refrigerator may out perform double-effect H2O/LiBr systems. The authors' experimental results show that a COP of 1.013 is achievable when 200 °C steam is used to drive the refrigerator.

Details

  • Original title: An experimental investigation of ejector re-compression absorption refrigerator.
  • Record ID : 2002-2307
  • Languages: English
  • Source: Inst. Refrig., Adv. Proof - 8 p.; fig.; 4 ref.
  • Publication date: 2002/01/10
  • Document available for consultation in the library of the IIR headquarters only.