Capacity measurements with zeotropic FC-blend R407C.

[In German. / En allemand.]

Author(s) : AHNEFELD G., WOBST E.

Type of article: Article

Summary

Available with ILK is an experimental FC-, FC-blend plant, which can be used for industrial plant tests under nearly practical conditions. As compared with R22, performance measurements of plants operated with the zeotropic FC-blend R407C (R32, R125, R134a, at 23, 25, and 52%: AC9000, Klea 66, HX3) under constant external conditions (temperature difference 5 K between refrigerant/heat carrier, constant refrigerating capacity) showed losses of up to 25% for the COP. The worst values were obtained on tube-bundle types.

Details

  • Original title: [In German. / En allemand.]
  • Record ID : 1996-1437
  • Languages: German
  • Source: KI Luft Kältetech. - vol. 31 - n. 3
  • Publication date: 1995/03
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (4)
See the source