Combustion turbine inlet air cooling: benefits and technology options in district energy applications.

Author(s) : ANDREPONT J. S.

Summary

The paper presents the concepts and benefits of cooling the inlet air entering CTs (combustion turbines) during times of high ambient air temperature. Actual examples are presented of CTIAC (combustion turbine inlet air cooling) in district energy applications, illustrating the various technologies. During hot weather, CTIAC can typically achieve a CT power output improvement of 20 to 30%, as well as an efficiency improvement of 5%. CTIAC unit capital costs are often roughly half those of equivalent simple cycle CTs. Further enhanced cost benefits are described that are achievable when CTIAC is coupled with district cooling systems. CTIAC is projected to be of increasing value in future deregulated electric power environments.

Details

  • Original title: Combustion turbine inlet air cooling: benefits and technology options in district energy applications.
  • Record ID : 2002-1624
  • Languages: English
  • Source: ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
  • Publication date: 2001
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (60)
See the conference proceedings