Commercial absorption chiller models for evaluation of control strategies.

Summary

A steady-state computer simulation of a direct-fired, double-effect water-lithium bromide absorption chiller in the parallel-flow configuration was developed from first principles. Unknown model parameters such as heat-transfer coefficients were determined by matching the model's calculated state points and COP against nominal full-load operating data and COPs obtained from a manufacturer's catalog. The model compares favorably with the manufacturer's performance ratings for varying water circuit (chilled and cooling) temperatures at full-load conditions and for chiller part-load performance.

Details

  • Original title: Commercial absorption chiller models for evaluation of control strategies.
  • Record ID : 1996-2228
  • Languages: English
  • Source: ASHRAE Transactions.
  • Publication date: 1995/01
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles from the proceedings (70)
See the conference proceedings