IIR document

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution and compensation.

Author(s) : KAERN M. R., ELMEGAARD B., LARSEN L. F. S.

Type of article: Article, IJR article

Summary

Flow maldistribution in fin-and tube evaporators for residential air-conditioning is investigated by numerical simulation. In particular, the interlaced and the face split evaporator are compared in flow maldistribution conditions. The considered sources of maldistribution are the liquid/vapor distribution and the airflow distribution. Furthermore, compensation of flow maldistribution by control of individual channel superheat is studied for each evaporator type. It is shown that the interlaced evaporator is better at flow maldistribution than the face split evaporator. However, if individual channel superheats are controlled, the face split evaporator achieves the best performance, i.e. an increase of 7% in overall UA-value and 1.6–2.4% in COP compared to the interlaced evaporator without compensation.

Available documents

Format PDF

Pages: 203-214

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution and compensation.
  • Record ID : 30006480
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 1
  • Publication date: 2013/01

Links