DAMAGE TO EVAPORATORS ON THE WATER SIDE.

[In German. / En allemand.]

Author(s) : MENZE K.

Type of article: Article

Summary

THE MANUFACTURING PROCESS OF COAXIAL EVAPORATORS IS DESCRIBED ; DAMAGE PROBLEMS ARE REPORTED (45 FOR THE 40,000 UNITS SOLD BY WIELAND-WERKE). THE AUTHOR STRESSES THE DAMAGES DUE TO CORROSION AND THE ROLE THAT MAY BE PLAYED BY THE COPPER OF EVAPORATORS AND THE DAMAGE DUE TO CORROSION-EROSION RESPONSIBLE FOR THE LARGEST NUMBER OF DAMAGES AND ITS CAUSES, MAINLY HIGH PUMPING RATES AND PUMPING OF A WATER/AIR MIXTURE INSTEAD OF WATER. A SERIES OF CONDITIONS TO BE MET IN ORDER STILL TO IMPROVE THE QUALITY OF PLANT AND PREVENT DAMAGE IN THE FUTURE ARE GIVEN. R.R.

Details

  • Original title: [In German. / En allemand.]
  • Record ID : 1986-0143
  • Languages: German
  • Source: Temp. Tech. - vol. 23 - n. 1
  • Publication date: 1985/01
  • Document available for consultation in the library of the IIR headquarters only.

Links


See other articles in this issue (1)
See the source