Recommended by the IIR / IIR document

Detection of R290 leaks in RACHP equipment using ultrasonic sensors.

Author(s) : COLBOURNE D., VONSILD A. L.

Type of article: IJR article

Summary

There is a growing need for cost-effective leak detection in smaller RACHP equipment that uses R290 and other flammable hydrocarbon refrigerants. Gas detection technology may not be suitable in many cases due to cost and reliability implications whilst detection with system parameters can suffer long response times. Ultrasonic leak detection can be an economical and reliable method. This study presents the development and testing of an ultrasonic leak detector using off-the-shelf components, within a conventional split type wall-mounted air conditioner indoor unit. Depending upon the chosen sensor, a fast and effective response to simulated “small” R290 leaks was achieved. Measurements of potential interference from environmental noise across ultrasonic frequencies suggests false alarms are unlikely. Such a leak detector was found to be potentially effective.

Available documents

Format PDF

Pages: 342-353

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Detection of R290 leaks in RACHP equipment using ultrasonic sensors.
  • Record ID : 30031910
  • Languages: English
  • Subject: Technology
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 151
  • Publication date: 2023/07
  • DOI: http://dx.doi.org/10.1016/j.ijrefrig.2023.03.015

Links


See other articles in this issue (33)
See the source