Distribution air conditioning systems. Application to an industrial building with high energy demands.
Climatizzazione con sistema a dislocamento. Aplicazione in uno stabilimento industriale ad alta densità energetica.
Author(s) : CURCULACOS G., SIMION C.
Type of article: Article
Summary
This paper shows the preliminary analyses, the calculation algorithms and the technical criteria adopted when designing a heat control system for a new production line in an industrial unit manufacturing plastic films through high temperature processes. This is in air conditioning installation equipped with distribution systems with the following main parameters: volume of the building: about 30,000 m3; inflow of external air: about 420,000 m3; maximum environmental load: about 1400 kW frigo; refrigerating power: about 4.5 MW. The simulation algorithms used for assessing loads, making subsequent design choices and evaluating the experimental results in the first years are described in detail. Some interesting points about distribution systems emerge.
Details
- Original title: Climatizzazione con sistema a dislocamento. Aplicazione in uno stabilimento industriale ad alta densità energetica.
- Record ID : 2001-0407
- Languages: Italian
- Source: Cond. Aria - vol. 44 - n. 4
- Publication date: 2000/04
- Document available for consultation in the library of the IIR headquarters only.
Links
See other articles in this issue (1)
See the source
Indexing
- Themes: Other air-conditioning equipment
- Keywords: Plastic; Industrial application; High capacity; Manufacture; Process; Monograph; Film; Air conditioning
-
World trends of chillers and large air-conditio...
- Date : 1997/11/25
- Languages : English
- Source: JARN - vol. 29 - n. 11
View record
-
Chillers and large air conditioning equipment: ...
- Date : 2000/11/25
- Languages : English
- Source: JARN - vol. 32 - n. 11
View record
-
Design and design management of very large buil...
- Author(s) : MACDONALD M.
- Date : 1998/01
- Languages : English
- Source: S. A. Refrig. Aircond. - vol. 14 - n. 1
View record
-
Industrie : l'ambiance compte autant que le pro...
- Author(s) : PISANI S.
- Date : 2000/03
- Languages : French
- Source: CLIM Prat. - n. 29
View record
-
Climatiseurs réversibles, individuels, résident...
- Date : 1993/12
- Languages : French
- Source: La revue pratique du froid et du conditionnement d'air - n. 786
View record