Evaporation and condensation of HFC-134a and CFC-12 in a smooth tube and a micro-fin tube.
Author(s) : ECKELS S. J., PATE M. B.
Summary
Evaporation and condensation heat transfer coefficients were measured for smooth and micro-fin tubes with R134a and R12. Micro-fin tubes are internally enhanced tubes that are characterized by numerous small fins that spiral down the tube. For example, in this study, the micro-fin tube had 60 fins with a height of 0.2 millimeters and a 17 deg spiral angle. Heat transfer measurements were performed on 3.67 meters long tubes with inside diameters of 8.0 millimeters. Test conditions varied from 5 to 15 deg C for evaporation and 30 to 50 deg C for condensation. The refrigerant mass flux was varied from 130 to 400 kilogrammes/m2.second.
Details
- Original title: Evaporation and condensation of HFC-134a and CFC-12 in a smooth tube and a micro-fin tube.
- Record ID : 1993-0808
- Languages: English
- Publication date: 1991
- Source: Source: ASHRAE Trans.
vol. 97; n. 2; 71-81; 14 fig.; 7 tabl.; 15 ref. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Mass transfer
- Keywords: R134a; Internal fin; Heat transfer coefficient; Microfin tube; Measurement; Heat transfer; Bare pipe; R12; Evaporation; Condensation
-
Condensation heat transfer of R22 and R410A in ...
- Author(s) : KIM M. H., SHIN J. S., LIM B. H.
- Date : 2002/08/26
- Languages : English
- Formats : PDF
View record
-
Evaporation of R22 in a 7-mm microfin tube.
- Author(s) : KUO C. S., WANG C. C., CHENG W. Y., LU D. C.
- Date : 1995/06/24
- Languages : English
- Source: ASHRAE Transactions.
View record
-
Heat transfer coefficients and pressure drops f...
- Author(s) : ECKELS S. J., DOERR T. M., PATE M. B.
- Date : 1998
- Languages : English
- Source: ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
View record
-
ENHANCEMENT OF IN-TUBE CONDENSATION OF NON-AZEO...
- Author(s) : KOYAMA S., GAO L., FUJII T.
- Date : 1991/08/10
- Languages : English
- Source: New challenges in refrigeration. Proceedings of the XVIIIth International Congress of Refrigeration, August 10-17, 1991, Montreal, Quebec, Canada.
- Formats : PDF
View record
-
A COMPARISON OF 150 AND 300 SUS OIL EFFECTS ON ...
- Author(s) : SCHLAGER L. M., PATE M. B., BERGLES A. E.
- Date : 1989
- Languages : English
View record